Home - Product Center- Suspended dry powder fire extinguishing device

Contact us

Phone: 0516-87927835

Email: 429713823@qq.com

Address: Huangshi Road, Gulou District, Xuzhou City, Jiangsu Province

Fax: 0516-87933292


prev
next

Suspended ultrafine dry powder fire extinguishing device series

2020-10-10 16:57:24

product details

1. Introduction

FZXA4/1.2 (ultra-fine) and FZXA8/1.2 (ultra-fine) suspended ultra-fine dry powder fire extinguishing devices are composed of tanks, temperature-sensitive glass nozzles, pressure indicators, suspension rings, etc. The tank is filled with ABC ultra-fine dry powder fire extinguishing agent, filled with an appropriate amount of driving gas nitrogen, and its technical performance meets the requirements of the GA602-2006 standard. The nozzle of the device is equipped with a temperature-sensitive glass nozzle. When a fire occurs, the temperature rises to the set operating temperature of 68℃. The liquid in the glass ball expands, causing the glass to swell and break. The ABC ultra-fine dry powder fire extinguishing agent in the tank is driving the gas nitrogen. When pushed, it will spray out for automatic fire extinguishing.

FZXA4/1.2 (ultra-fine) type, FZXA8/1.2 (ultra-fine) type suspended ultra-fine dry powder fire extinguishing device has the advantages of high fire extinguishing efficiency, low corrosiveness, good insulation performance, no pipeline, wireless circuit, and reasonable structure. In particular, the ABC ultra-fine dry powder fire extinguishing agent in the tank has zero depletion potential (ODP) of the atmospheric ozone layer and zero greenhouse effect potential (GMP). The extinguishing agent can naturally prevent moisture, has a long shelf life, and has high fire extinguishing efficiency. It is not only used for full-submerged fire extinguishing in relatively closed spaces, but also used for partial protection and fire fighting in open places. The fire extinguishing efficiency per unit volume is 6 times that of ordinary dry powder fire extinguishing agents.

FZXA4/1.2 (ultra-fine) type, FZXA8/1.2 (ultra-fine) type suspended ultra-fine dry powder fire extinguishing device is suitable for oil depots, paint warehouses, power distribution rooms, drying rooms, some closed places and other places where no one works. One of the indoor automatic fire extinguishing equipment.

2. Main performance parameters


specification/parameter

Extinguishing agent weight

kg

Filling nitrogen pressure at 20℃

MPa

Spray time

S

Injection remaining rate

%

Action temperature

Operating temperature

Fire extinguishing level

Protected area/volume

㎡/ m3

FXZ-ACT4/1.2

4-50%

1.2

≤5

≤5

68

-10~+50

1A 34B

7.3

FXZ-ACT5/1.2

5-50%

1.2

≤5

≤5

68

-10~+50

1A 34B

9.12

FXZ-ACT6/1.2

8-50%

1.2

≤10

≤5

68

-10~+50

2A 55B

10.9 




3. Schematic diagram of suspended fire extinguishing device

1. Hanging rings

2. Tank body (with ABC dry powder fire extinguishing agent, filled with driving gas nitrogen)

3. Pressure indicator

4. Temperature sensing glass nozzle

悬挂式超细干粉灭火装置系列1.jpg

 

4. Instructions for installation, use and maintenance

1. The suspension point of the fire extinguishing device should be selected at a location prone to fire in the protection zone or above the object to be protected, and the suspension height should be more than 1 meter above the protected object, but should not exceed 3 meters.

2. The fire extinguishing device is a pressure-storage container, and collisions should be avoided during transportation and storage. The environment in the protection area of the fire extinguishing device should be dry and ventilated to prevent freezing, dampness, rain and sun exposure.

3. The storage temperature of the fire extinguishing device is -10℃~+50℃.

4. When the user starts to set up the fire extinguishing device, he should check at quarterly intervals and find that the pressure indicator is not in the green area or should be sent to the maintenance unit for repair once it is used.

5. The fire extinguishing device must undergo a 2.1MPa water pressure test every time it is refilled or every 5 years, and it can be used only after it is qualified.

6. When the fire extinguishing device is repaired and refilled, our company provides priority services.